CISSP subtopic 3.8, Domain 33.8 Apply security principles to site and facility design

This subtopic belongs to Domain 3, "Security Architecture and Engineering", which weighs 13% of the exam. Our bank holds 12 questions on it, split by difficulty as follows.

Theory in the Official Study Guide (10th ed.): chapter 10.

What gets asked on this subtopic

Concepts and situations that appear in our questions for this objective. The exam nearly always frames them as cases where you must decide.

  • CPTED
  • Natural surveillance
  • Site selection factors
  • Data center placement in building
  • True floor to true ceiling
  • Physical controls: deter, detect, assess, respond
  • Secure facility plan
  • Visibility of facility
  • Security vs life safety
  • Layered physical defense
  • Balancing CPTED and controls
  • Shared building risks

Sample question

Domain 3/3.8 Apply security principles to site and facility design

During a walk-through of a bank's secure records room, Federica notices that its walls stop at the drop ceiling, leaving open space above them. What is the MAIN security concern?

  1. AConversations may be overheard from next door
  2. BIntruders can bypass the door over the walls
  3. CListening devices may be hidden above the tiles
  4. DNetwork cables in the void may be tapped
Show the answer

Correct answer: B. The question asks why partial-height walls weaken a secure room. The clue is that "its walls stop at the drop ceiling". Walls of secure areas should run from the true floor to the true ceiling, slab to slab, so that nobody can enter over the ceiling tiles or under a raised floor. Otherwise the door's locks and readers can simply be bypassed.

  • A. Incorrect. Sound can travel over partial walls, but this is a records room, not a meeting room, so the main threat is physical entry.
  • B. Correct. Walls that stop at the drop ceiling let someone lift a tile and climb over from the next room, bypassing the door controls.
  • C. Incorrect. Hidden listening devices are a risk in any ceiling space, whether or not the walls reach the true ceiling.
  • D. Incorrect. Cables in the ceiling void can be tapped, but that risk does not depend on the height of the room's walls.